一、總述

金泉電力了解到配電(dian)(dian)(dian)(dian)房(fang)是供(gong)電(dian)(dian)(dian)(dian)系統中的(de)關(guan)鍵部位,我們平時說(shuo)的(de)配電(dian)(dian)(dian)(dian)房(fang)其實是對各(ge)種變(bian)(bian)(bian)配電(dian)(dian)(dian)(dian)所(suo)(suo)(suo)(suo)、配電(dian)(dian)(dian)(dian)室的(de)統稱(cheng)。35KV變(bian)(bian)(bian)配電(dian)(dian)(dian)(dian)所(suo)(suo)(suo)(suo)包括35/10(6)kV變(bian)(bian)(bian)電(dian)(dian)(dian)(dian)所(suo)(suo)(suo)(suo)和35/0.38kV變(bian)(bian)(bian)電(dian)(dian)(dian)(dian)所(suo)(suo)(suo)(suo) 。 10(6)kV配電(dian)(dian)(dian)(dian)所(suo)(suo)(suo)(suo)(簡(jian)稱(cheng)配電(dian)(dian)(dian)(dian)所(suo)(suo)(suo)(suo)),有些地(di)方又稱(cheng)開閉所(suo)(suo)(suo)(suo),用戶單(dan)位內的(de)配電(dian)(dian)(dian)(dian)所(suo)(suo)(suo)(suo)常帶有10(6)kV變(bian)(bian)(bian)電(dian)(dian)(dian)(dian)所(suo)(suo)(suo)(suo); 10(6)kV變(bian)(bian)(bian)電(dian)(dian)(dian)(dian)所(suo)(suo)(suo)(suo)(簡(jian)稱(cheng)變(bian)(bian)(bian)電(dian)(dian)(dian)(dian)所(suo)(suo)(suo)(suo)),指高壓(ya)側電(dian)(dian)(dian)(dian)壓(ya)為10(6)kV的(de)變(bian)(bian)(bian)電(dian)(dian)(dian)(dian)所(suo)(suo)(suo)(suo),在工業(ye)企(qi)業(ye)內又稱(cheng)車間變(bian)(bian)(bian)電(dian)(dian)(dian)(dian)所(suo)(suo)(suo)(suo),變(bian)(bian)(bian)電(dian)(dian)(dian)(dian)所(suo)(suo)(suo)(suo)一般由變(bian)(bian)(bian)壓(ya)器,高壓(ya)室,低壓(ya)室等(deng)部分組成。


二、變配電所選址

1.盡量(liang)(liang)接(jie)近負荷中心,以降(jiang)低配電配電系統的(de)電能(neng)損(sun)耗、電壓損(sun)耗和(he)有(you)色金屬消耗量(liang)(liang);

2.進(jin)出方便,特別是要便于架空進(jin)出線;

3.接近電源側,特別是工廠的總降壓(ya)變電所(suo)和高壓(ya)配電所(suo);

4.設備運輸方便(bian),特別是要考慮電(dian)力變壓(ya)器和高低壓(ya)成(cheng)套配電(dian)裝置的運輸;

5.不應設(she)在有(you)劇烈振(zhen)動或高溫的場所,當無法避開時,應有(you)防振(zhen)和隔熱的措(cuo)施;

6.不宜設在多塵(chen)或有腐(fu)蝕性氣(qi)體的(de)場所,無法遠(yuan)離時,不應設在污染源的(de)下風側;

7.不(bu)應設在廁所、浴室(shi)和其他(ta)經常積水場所的正下方(fang),且不(bu)宜與上(shang)述場所相(xiang)貼鄰(lin);

8.不應設(she)在有爆炸危險(xian)環境(jing)的正(zheng)上方(fang)(fang)或正(zheng)下方(fang)(fang),且不宜設(she)在有火災危險(xian)環境(jing)的正(zheng)上方(fang)(fang)或正(zheng)下方(fang)(fang)。

9.不(bu)應設在地勢低洼和可能積水的場所。

10.配電所(suo)一般為獨立式建筑(zhu)物(wu),也可(ke)以(yi)與所(suo)帶10(6)KV變電所(suo)一起附設于(yu)負荷較大的廠房或建筑(zhu)物(wu)。


三、變配電所(suo)的布(bu)置

①布置緊湊合理,便于(yu)設備(bei)的操作(zuo)、搬運(yun)、檢修、試驗和(he)巡視(shi),還要考慮發展的可能性。

②適當安排建筑物內各房間的相(xiang)對位置,使(shi)配電室的位置便于進出線。

③盡量利用(yong)自然(ran)采光和自然(ran)通風,變壓器(qi)室和電容器(qi)室盡量避免(mian)西曬,控(kong)制室盡可能朝南。

④配電室(shi)、控制(zhi)室(shi)、值(zhi)班室(shi)等的地(di)面宜(yi)高出(chu)室(shi)外地(di)面150~300mm,當附設于車間內時(shi),則可與(yu)車間的地(di)面相平。

⑤10kV配(pei)變電所宜(yi)單(dan)層(ceng)布(bu)置(zhi),當(dang)采用雙層(ceng)布(bu)置(zhi)時,變壓(ya)器室(shi)應(ying)設在(zai)底層(ceng),并且二層(ceng)的配(pei)電室(shi)需留(liu)有(you)吊裝(zhuang)設備的吊裝(zhuang)孔,吊裝(zhuang)平臺等。

⑥不帶可燃性油的高、低(di)壓(ya)配(pei)電(dian)裝置(zhi)和非油浸(jin)的全(quan)封(feng)閉型變(bian)壓(ya)器(qi)可設(she)在同一房(fang)間內,具有IP3X防護等級外殼的配(pei)電(dian)柜和非油浸(jin)全(quan)封(feng)閉變(bian)壓(ya)器(qi)可靠近布置(zhi)在配(pei)電(dian)房(fang)內。

⑦配電室(shi)、變壓器(qi)室(shi)、電容(rong)器(qi)室(shi)的門應(ying)向(xiang)外開(kai),相鄰配電室(shi)有門時(shi),該門應(ying)能雙向(xiang)開(kai)啟或向(xiang)低壓室(shi)側開(kai)啟。

⑧油(you)(you)變(bian)(bian),高壓(ya)電(dian)容器柜(ju)和多油(you)(you)斷路器柜(ju)等宜設(she)(she)置(zhi)在高層(ceng)建(jian)筑外的(de)專用(yong)房間內(nei),當條件受(shou)到限制必須設(she)(she)置(zhi)在高層(ceng)建(jian)筑或其裙房內(nei)時,可燃油(you)(you)油(you)(you)浸變(bian)(bian)壓(ya)器總容量(liang)(liang)不(bu)應超過(guo)1260KVA,單臺容量(liang)(liang)不(bu)應超過(guo)630KVA(變(bian)(bian)壓(ya)器下應設(she)(she)有儲(chu)存變(bian)(bian)壓(ya)器全部油(you)(you)量(liang)(liang)的(de)事(shi)故儲(chu)油(you)(you)設(she)(she)施,并(bing)且其他各功能室應設(she)(she)置(zhi)防止油(you)(you)品流散的(de)設(she)(she)施)。


四、各配(pei)電室的布置(zhi)

1>高壓(ya)室

①帶可(ke)燃性油的高壓(ya)配(pei)(pei)電(dian)裝(zhuang)(zhuang)置,宜裝(zhuang)(zhuang)設(she)單獨配(pei)(pei)電(dian)室;10(6)kV高壓(ya)開關柜數量為6臺以下(xia)時,可(ke)與低壓(ya)配(pei)(pei)電(dian)屏設(she)同一房間。

②高(gao)壓(ya)配電(dian)室宜預(yu)留開關柜(ju)備用(yong)位置(zhi)。


五、金(jin)泉電力(li)談及高低(di)壓母線橋架的做法

①單排(pai)開關柜(ju)中間(jian)斷開時(因(yin)安(an)全間(jian)距需要),或雙排(pai)開關柜(ju)有(you)母(mu)聯時;變壓器與進線柜(ju)間(jian)母(mu)排(pai)連接(jie) ,一般用母(mu)線橋的方式

②注(zhu)意母線橋的高(gao)度(du)(底)應略高(gao)于開關柜安裝后的高(gao)度(du),并且留(liu)出檢修(xiu)維護空間,

③母(mu)線(xian)橋比較(jiao)適用(yong)于開關柜頂置母(mu)線(xian),

④注意(yi)母(mu)(mu)線橋中母(mu)(mu)線的安(an)裝固定(ding),須注意(yi)穩定(ding)方(fang)面,畢(bi)竟它是(shi)非標加(jia)工產品,不注意(yi)的話容(rong)易出質量問題;

⑤最(zui)后,對(dui)于抽出式開關(guan)柜(ju),標準系列的框架配件有一(yi)定的機械強度限制,母線橋如果過(guo)(guo)重時,需要加強柜(ju)體支撐力,同時,母線橋也不宜過(guo)(guo)長(chang),否則容(rong)易變形。


金泉電力